5-40
FP-e (A: Available, N/A: Not available)
Register
No.
Name
Descriptions
Read
-ing
Writ
-ing
DT9054
Real-Time Clock
(Clock/Calendar)
setting
(minute/second)
DT9055
Real-Time Clock
(Clock/Calendar)
setting (day/hour)
DT9056
Real-Time Clock
(Clock/Calendar)
setting
(year/month)
DT9057
Real-Time Clock
(Clock/Calendar)
setting (day-of-the-
week)
The year, month, day, hour, minute, second and
day-of-the-week data for the Real-Time Clock
(Clock/Calendar) is stored. The built-in Real-
Time Clock(Clock/Calendar) will operate
correctly through the year 2099 and supports
leap years. The Real-Time Clock
(Clock/Calendar) can be set by writing a value
using a programming tool software or a program
that uses the F0 (MV) instruction.(see example
for DT90058)
A A
DT9058
Real-Time Clock
(Clock/Calendar)
time setting
By setting the highest bit of DT9058 to 1, the
time becomes that written to DT9054 to DT9057
by the F0 (MV) instruction. After the time is set,
DT9058 is cleared to 0. (Cannot be performed
with any instruction other than the F0 (MV)
instruction.)
<Example>
Set the time to 12:00:00 on the 5th day when
X0 turns on.
FPWIN GR:
If you changed the values of DT9054 to DT9057
with the programming tool software, the time will
be set when the new values are written.
Therefore, it is unnecessary to write to DT9058.
A A
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...