High
−
level Instructions
3
−
762
Flag conditions
・
Error flag (R9007): Turns on and stays on when:
・
Error flag (R9008): Turns on for an instant when:
−
The value set for the parameter is out of range.
−
The area specified using the index modifier exceeds the limit.
Parameter table settings
[S]
Control mode
[S+1]
Set value (SP)
[S+2]
Measured value (PV)
[S+3]
Output value (MV)
[S+4]
Output lower limit
[S+5]
Output upper limit
[S+6]
Proportional gain (Kp)
[S+29]
[S+7]
Integral time (Ti)
[S+8]
Derivative time (Td)
[S+9]
Control cycle (Ts)
[S+10]
Auto-tuning progress
[S+11]
PID processing work area (
*
)
*
For the FP0 use the 20 words, [S+11] to [S+30], as the work area.