High
−
level Instructions
3
−
548
Outline
Pulses area output from channel for 2 pulse output, in accordance with
the parameters in the designated data table, so that the path to the
target position forms a straight line.
Program example
Ladder Diagram
Boolean
Ladder Diagram
Address
Instruction
10
F175 SPSH , DT100 , K 0
S
n
R10
DF
10
11
12
ST
R
10
DF
F175
(SPSH)
DT
100
K
0
S
Starting 16
−
bit area for registering data tables
n
Channels intended for pulse output (n=0 to 3)
Operands
Operand
Relay
Timer/Counter Register
Index
register Constant
Index
modifier
Operand
WX WY WR
SV
EV
DT
I
H
modifier
S
N/A N/A N/A
N/A
N/A
A
N/A
N/A
A
n
N/A N/A N/A
N/A
N/A
N/A
N/A
A
N/A
Description
When the corresponding pulse output instruction flag is off and the trigger is on, pulses are output from
channel ch0 (X
−
axis) and ch2 (Y
−
axis), or ch
3
(X
−
axis) and ch
4
(Y
−
axis).
Channel no.
Output
Output method
ch0 (for X
−
axis)
Y0
CW
PLS
(
)
Y1
CCW
SIGN
ch2 (for Y
−
axis)
Y3
CW
PLS
(
)
Y4
CCW
SIGN
ch3 (for X
−
axis)
Y5
CW
PLS
(
)
Y6
CCW
SIGN
ch4 (for Y
−
axis)
Y7
CW
PLS
(
)
Y8
CCW
SIGN
The control code, initial speed, maximum speed, acceleration/deceleration time, and target value are
specified by creating the data table ”S” to ”S+11” on the following page using the user program.
When the elapsed value reaches the final target value, the pulse output stops.
FP0R
Pulse output
(Linear interpolation)
5
F175
(SPSH)
Availability
FP0R
A: Available
N/A: Not Available
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...