5-161
FP2/FP2SH/FP10SH
Item
Add-
ress
Name
Default
value
Descriptions
MEWNET
-H
setting
49
Processing capacity
setting for PC link of
MEWNET-H link system
Available PLC: FP10SH
4
(1024
bytes per
scan)
0: All data in a scan
1 to 65535: Setting processing
capacity per scan can be obtained
using the formula “Capacity” = “Set
value” x 256 bytes
50
Size of link
relays used
for commu-
nication
0
0 to 64 words
51
Size of link
data
registers
used for
commu-
nication
0
0 to 128 words
52
Send area
starting
address of
link relay
64
64 to 127
53
Size of link
relays used
for send
area
0
0 to 64 words
54
Send area
starting
address of
link data
register
128
128 to 255
PC link 1
setting
55
PC link 1
settings for
MEWNET-
W/-P link
system
Available
PLC:
MEWNET-
W:
FP10SH,
FP2,
FP2SH
MEWNET-
P:
FP10SH
Size of link
data
registers
used for
send area
0
0 to 127 words
410
Unit number setting for
tool port
Available PLC: FP2/
FP2SH
1
1 to 99 (unit No. 1 to 99)
Tool port
setting
411
Communication format
setting for tool port
Available PLC: FP2/
FP2SH
Commu-
nication
format
(character
bit): 8 bits,
Modem
communi-
cation:
Disabled
Character bits: 7 bits/8bits
Modem communication:
Enabled/Disabled
When connecting a modem, set the
unit number to 1 with system register
410.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...