High
−
level Instructions
3
−
408
Precautions during programming
It is not possible to execute multiple
F152 (RMRD)
instructions and
F153 (RMWT)
instructions at one time.
The program should be set up so that these instructions are executed when the
F152 (RMRD)/F153 (RMWT)
instruction execution enabled flag (R9035) is on.
R9035
0: Execution inhibited (
RMRD/RMWT
instruction being executed)
1: Execution enabled
The
F152 (RMRD)
instruction only enables a request to be sent. The actual processing is carried out with the
ED
instruction. The
F152 (RMRD)/F153 (RMWT)
instruction completed flag (R9036) can be used to confirm
whether or not the instruction has been executed.
R9036
0: Completed normally
1: Completed with error (The error code is stored in DT9036
/
DT90036)
DT9036
(DT90036)
If the transmission has been completed with an error (R9036 is on), the contents of the error (error
code) are stored.
Reference: The error codes stored in the DT9036/DT90036
Error code (HEX) Description
H5B
Time
−
out error (no intelligent unit found at the specified location.)
H68
No memory error (no memory exists at the specified address.)
H71
Send answer time
−
out error
H72
Send buffer full time
−
out error
H73
Response time
−
out error
If the error code is H71 to H73, a communication time
−
out error has occurred. The time
−
out time can be
changed within a range of 10.0 ms to 81.9 s (in units of 10 ms), using the setting of system register 32. The
default value is set to 2 seconds for FP3 and 10 seconds for FP2/FP2SH/FP10SH.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...