High
−
level Instructions
3
−
493
Outline
This instruction outputs pulses from the specified channel for the pulse
output according to the specified parameters.
Program example
Ladder Diagram
Boolean
Ladder Diagram
Address
Instruction
10
F171 SPDH , DT100 , K 0
S
n
Trigger
R10
DF
10
11
12
ST
R
10
DF
F171
(SPDH)
DT
100
K
0
S
Starting address of area containing the data table.
n
Channel for pulse output.
Operands
Operand
Relay
Timer/Counter Register
Index
register
Constant
Index
modifier
Operand
WX WY WR
SV
EV
DT
I
K
H
modifier
S
N/A N/A N/A
N/A
N/A
A
N/A
N/A N/A
A
n
N/A N/A N/A
N/A
N/A
N/A
N/A
A
A
N/A
Description
Pulses are output from the specified channel when the corresponding control flag turns off and the excution
condition is in on state.
For FP
Σ
For FP
−
X Ry type (AFPX
−
PLS)
Channel no.
Output
Output method
Channel no.
Output
Output method
ch0
Y0
CW
PLS
ch0
Cassete
Y100
CW
PLS
Y1
CCW
SIGN
Cassete
mounting part 1
Y101
CCW
SIGN
ch2
Y3
CW
PLS
ch1
Cassete
Y200
CW
PLS
Y4
CCW
SIGN
Cassete
mounting part 2
Y201
CCW
SIGN
For FP
−
X Tr type
Channel no.
Output
Output method
ch0
Y0
CW
PLS
Y1
CCW
SIGN
ch1
Y2
CW
PLS
Y3
CCW
SIGN
ch2
Y4
CW
PLS
Y5
CCW
SIGN
ch3
Y6
CW
PLS
Y7
CCW
SIGN
Note) There is no ch3 for C14T and C14TD.
Note) The pulse I/O cassette (AFPX
−
PLS) cannot be installed on the FP
−
X Tr type.
Note) Use the ch2 and ch3 at up to 20 kHz.
FP
Σ
/FP
−
X
Pulse output
(with channel specification)
(trapezoidal control)
5
F171
(SPDH)
Availability
FP
Σ
/FP
−
X
A: Available
N/A: Not Available
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...