Install a CPU
Ensure that the orientation is correct as damage might result if the CPU pins are not aligned
correctly.
4.
Lower the pressure frame.
Ensure that the pressure frame sits flat around the periphery of the CPU.
5.
Engage the release lever by rotating it downward and slipping it under the catch
[2].
6.
Use the syringe (supplied with the new or replacement CPU) to apply
approximately 0.1 ml of thermal grease to the center of the top of the CPU.
Do not distribute the grease, as the CPU heatsink pressure will do so for you.
7.
Inspect the heatsink for dust and lint.
Clean heatsink if necessary.