CHAPTER 5 PARAMETERS
E5EK
5--40
Operation at power ON
Selects one of the following operations when the power is turned ON:
•
“Continue” : Starts operations from the state that was active when the power
was
interrupted.
•
“Reset”
: Resets the controller.
•
“Run”
: Starts normal program operation.
•
“Manual” : Sets the controller to the manual mode.
“Manual” cannot be selected when Auto/Manual key operation is protected.
Setting Range
Default
“
” :Continue/ “
” :Reset/ “
” Run/ “
” :Manual
F
Related description
4.7 Setting Running Conditions/Operation at power ON (page 4-14)
End condition
•
Specifies a reset state or continued control on the SP of the final step after pro-
gram operation ends.
•
The program end state will not change when the “number of steps” parameter
setting has been changed after program operation ends. However, when control on
the SP is continued, the SP of the final step is selected after the number of steps
has been changed.
Setting Range
Default
“
” :Reset/ “
” :Continued control using final SP
F
Related description
4.7 Setting Running Conditions/End condition (page 4-15)
F
Related parameter
“Number of steps” (program mode)