CHAPTER 5 PARAMETERS
E5EK
5--20
Position-proportional
dead band
Conditions of Use
The control must be position-propor-
tional control.
•
Sets the output hold width (ON/OFF switching point for open and close output)
during position-proportional control.
Setting Range
Unit
Default
0.1 to 10.0
%
2.0
F
Related description
4.1 Selecting the Control Method/Position-proportional control (page 4-3)
F
Related parameter
“Open/close hysteresis” (level 2 mode)
E5EK-TPRR2
Manual reset value
Conditions of Use
The control must be either standard con-
trol or advanced PID control, and the
“integral time” parameter must be set to
“0”.
•
Sets the required manipulated variable to remove offset during stabilization of P
or PD control.
Setting Range
Unit
Default
0.0 to 100.0
%
50.0
E5EK-TAA2
Level 1 Mode
Function
Setting
See
Model
Function
Setting
Model