CHAPTER 3 BASIC OPERATION
E5EK
3--4
3.2 Setting Input Specifications
Setting input specifications
Input type
Temperature input?
Temperature unit
Temperature input shift
End of setup
Decimal point
Scaling
Setup mode
Level 2 mode
N
Y
•
With temperature input, scaling and decimal point parameters need
not be set as this information is determined by the input (sensor)
type. (These parameters are not displayed.) Note that temperature
unit and temperature input shift parameters need to be set.
•
With analog input, the “scaling upper limit”, “scaling lower limit”
and “decimal point” parameters need to be set.
•
Set the type No. (0 to 21) in the “input type” parameter (Set up
mode). The factory setting is “2: K1 (thermocouple).”
•
For details on input types and setting ranges, see page 5-31.