CHAPTER 5 PARAMETERS
E5EK
5--34
Control output 1
assignment
Control output 2
assignment
Conditions of use
The control must be standard control or
heating and cooling control.
•
Assigns the output functions to either of control output 1 or 2.
•
The following 11 output functions can be assigned as outputs:
Control output (heat), Control output (cool), Alarms 1 to 3, HBA, LBA, Time sig-
nals 1 and 2, Program end and Stage output
•
When the output function assigned to control output 1 or control output 2 is ON,
the “OUT1” or “OUT2” LED lights. However, note that the “OUT1” or “OUT2”
LEDs do not light if the output unit is E53-C
VV
or E53-V
VV
when control output
(heat) or control output (cool) functions are assigned to control outputs.
Symbol
to
Function
Control output (heat)
Control output (cool)
Alarms 1 to 3
HBA
LBA
Symbol
to
Function
Time signals 1 to 2
Program end
Stage output
Default :
“Control output 1”= [
], “Control output 2”= [
].
F
Related description
3.3 Setting Output Specifications (page 3-7)
F
Related parameters
•
Alarm-related parameters
•
Heating and cooling related parameter
“Time signal 1 enabled step” “Time signal 2 enabled step” “Time signal 1 to 2 ON
time” “Time signal 1 to 2 OFF time” (program mode)
“LBA detection time” (level 2 mode)
E5EK-TAA2
Setup Mode
Function
Setting
See
Model
Summary of Contents for E5EK
Page 1: ...User s Manual Cat No H089 E1 02 Digital Controller Programmable Type...
Page 24: ...CHAPTER 1 INTRODUCTION 1 14...
Page 36: ...CHAPTER 2 PREPARATIONS 2 12...
Page 162: ...CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6 20...
Page 176: ...CHAPTER 7 CALIBRATION 7 14...
Page 193: ...SETTING LIST A 11...