6.4 Commands and Responses
E5EK
6--11
F
A group
Bit
Description
[1]
[0]
0
Heating side output
*3
ON
OFF
*1
1
Cooling side output
*4
ON
OFF
*1
2
Alarm output 1
ON
OFF
*2
3
Alarm output 2
ON
OFF
*2
4
Alarm output 3
ON
OFF
*2
5
LBA output
ON
OFF
*2
6
HBA output
ON
OFF
*2
7
Run/Reset
Reset
Run
8
Auto/Manual
Manual
Auto
9
Remote/Local
Remote
Local
10
11
AT
AT execution
OFF
12
Hold
During hold
OFF
13
Wait
During wait
OFF
14
15
F
B group
Bit
Description
[1]
[0]
0
Setting level
1
0
1
2
Control output 1 type
Linear
Pulse
3
Control output 2 type
Linear
Pulse
4
5
Input error
ON
OFF
6
A/D converter error
ON
OFF
7
CT overflow
ON
OFF
8
CT hold
ON
OFF
*5
9
Potentiometer error
ON
OFF
10
11
Time signal 1 output
ON
OFF
*2
12
Time signal 2 output
ON
OFF
*2
13
Ramp/soak
Ramp
Soak
14
Program end
ON
OFF
*6
15
During standby
ON
OFF
*1 Always “OFF” at linear output
*2 Always “OFF” when output is not assigned
*3 During position-proportional control, output is Open.
*4 During position-proportional control, output is Close.
*5 When the ON time during control output is less than 190 ms, the heater current to
which
“ 1” is set and the previous current value is held.
*6 “ON” while the No.2 display indicates [
]. For details on the [
] indication,
see page 4-15.
To return to setting level 0 from setting level 1, issue the “software reset” com-
mand. If the parameter write command is issued for the setup, expansion and
option modes in setting level 0, an error occurs, and the end code (0D = Com-
mand cannot be executed) is returned.
About Setting Levels
Summary of Contents for E5EK
Page 1: ...User s Manual Cat No H089 E1 02 Digital Controller Programmable Type...
Page 24: ...CHAPTER 1 INTRODUCTION 1 14...
Page 36: ...CHAPTER 2 PREPARATIONS 2 12...
Page 162: ...CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6 20...
Page 176: ...CHAPTER 7 CALIBRATION 7 14...
Page 193: ...SETTING LIST A 11...