CHAPTER 5 PARAMETERS
E5EK
5--36
Alarm 1 type
Alarm 2 type
Alarm 3 type
Conditions of Use
Alarms must be assigned as outputs.
For example, if alarm output 1 and 2
only are assigned as outputs, the “alarm
3 type” parameter cannot be used.
•
“Alarm 1 to 3 type” parameters specify the operation of the alarm by the one of
the set values in the following table. For details of operation at an alarm, see page
3-10.
Set Value
Settings
Set Value
Settings
1
Upper- and lower-limit alarm
7
Lower-limit alarm with standby sequence
2
Upper-limit alarm
8
Absolute-value upper-limit alarm
3
Lower-limit alarm
9
Absolute-value lower-limit alarm
4
Upper- and lower-limit range
alarm
10
Absolute-value upper-limit alarm with
standby sequence
5
Upper- and lower-limit alarm with
standby sequence
11
Absolute-value lower-limit alarm with
standby sequence
6
Upper-limit alarm with standby
sequence
Default is “2 : upper limit”.
F
Related description
3.4 Setting Alarm Type (page 3-10)
F
Related parameters
“Alarm value 1” “Alarm value 2” “Alarm value 3” (Program mode)
“Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode)
“Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” “Con-
trol output 1 assignment” “Control output 2 assignment” “Auxiliary output 1
assignment” “Auxiliary output 2 assignment” (setup mode)
Setup Mode
Function
Setting
See
Summary of Contents for E5EK
Page 1: ...User s Manual Cat No H089 E1 02 Digital Controller Programmable Type...
Page 24: ...CHAPTER 1 INTRODUCTION 1 14...
Page 36: ...CHAPTER 2 PREPARATIONS 2 12...
Page 162: ...CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6 20...
Page 176: ...CHAPTER 7 CALIBRATION 7 14...
Page 193: ...SETTING LIST A 11...