E5EK
5--39
Set point upper limit
Set point lower limit
•
Limits the upper and lower limits when the SP is set. The SP can be set within the
range defined by the upper and lower limit set values of the “set point upper
limit” and “set point lower limit ” parameters. Note that as these parameters are
reset, the SP of existing settings that are out of the range are forcibly changed to
one of the upper or lower limit values.
•
When the temperature input type and temperature unit have been changed, the
set point upper limit and set point lower limit are forcibly changed to the upper
and lower limits of the sensor.
•
During temperature input, the decimal point position is dependent on the cur-
rently selected sensor, and during analog input on the results of scaling.
Parameter
Setting Range
Unit
Default
Set point upper limit
Set point lower limit +1 to scaling upper limit
EU
1300
Set point lower limit
Scaling lower limit to set point upper limit -1
EU
-200
During temperature input, the range becomes the range of use of the selected sen-
sor instead of the range defined by the scaling upper and lower limit values.
F
Related description
4.2 Operating Condition Restrictions (page 4-7)
F
Related parameter
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup
mode)
PID/ON/OFF
Conditions of Use
The control must be standard control or
heating and cooling control.
•
Selects advanced PID control or ON/OFF control.
Setting Range
Default
“
” :Advance PID/ “
” :ON/OFF
F
Related description
4.1 Selecting the Control Method/ON/OFF control (page 4-5)
F
Related parameters
“Hysteresis (heat)” “Hysteresis (cool)” (level 1 mode)
E5EK-TAA2
Expansion Mode
Function
Setting
See
Function
Setting
See
Model
Summary of Contents for E5EK
Page 1: ...User s Manual Cat No H089 E1 02 Digital Controller Programmable Type...
Page 24: ...CHAPTER 1 INTRODUCTION 1 14...
Page 36: ...CHAPTER 2 PREPARATIONS 2 12...
Page 162: ...CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6 20...
Page 176: ...CHAPTER 7 CALIBRATION 7 14...
Page 193: ...SETTING LIST A 11...