E5EK
5--19
Cooling coefficient
Conditions of Use
The control must be either heating and
cooling control, or advanced PID control.
•
In heating and cooling control, P at the cooling side is calculated by the following
formula:
Cooling side P = Cooling coefficient x P
Setting Range
Unit
Default
0.01 to 99.99
None
1.00
F
Related description
4.1 Selecting the Control Method/Heating and cooling control (page 4-2)
F
Related parameter
“Proportional band” (level 1 mode)
E5EK-TAA2
Dead band
Conditions of Use
The control system must be heating and
cooling control.
•
Sets the output dead band width in a heating and cooling control system. A nega-
tive setting sets an overlap band.
Setting Range
Unit
Default
-19.99 to 99.99
%FS
0.00
F
Related description
4.1 Selecting the Control Method/Heating and cooling control (page 4-2)
E5EK-TAA2
Level 1 Mode
Function
Setting
See
Model
Function
Setting
See