CHAPTER 5 PARAMETERS
E5EK
5--44
α
Conditions of Use
The control must be advanced PID con-
trol.
•
Normally, use the default value.
•
Sets advanced PID-control parameter
α
.
Setting Range
Unit
Default
0.00 to 1.00
None
0.65
AT calculated gain
Conditions of Use
The control must be advanced PID con-
trol.
•
Normally, use the default value.
•
Sets the gain when adjusting the PID parameters by auto-tuning.
•
To give priority to response, decrease the set value of this parameter. To give
priority to stability, increase the set value of this parameter.
Setting Range
Unit
Default
0.1 to 10.0
None
1.0
F
Related parameter
“AT Execute/Cancel” (level 1 mode)
“PID/ON/OFF” (expansion mode)
F
Related parameter
“PID/ON/OFF” (expansion mode)
Expansion Mode
Function
Setting
Function
Setting
See