CHAPTER 5 PARAMETERS
E5EK
5--42
Time unit of ramp rate
Conditions of Use
Rate of rise programming must be set.
•
Specifies the unit time of “rate of rise 0 to 7.”
Setting Range
Default
“
” : Minute/ “
” : Hour
F
Related parameter
“Ramp rate 0 to 7” (program mode)
PV start
Conditions of Use
The set time must be set.
Specifies either of the following current SP at the start of program operation:
•
PV : Process value at start of program operation (PV start)
•
SP : SP of step 0 (normal program operation)
When “PV” is selected, program operation is started from the position where the
current SP first matches the PV at the start of program operation. If the SP does
not match the PV, program operation is started from the beginning of the program.
Setting Range
Default
“
” : PV/ “
” :SP
F
Related description
4.7 Setting Running Conditions/Starting the program run/PV start (page 4-20)