CHAPTER 4 APPLIED OPERATION
E5EK
4--4
•
Use the position-proportional type controller for position-proportion-
al control.
•
On a position-proportional type controller, control output 1 is used
for open output, and control output 2 is used for closed output. Ac-
cordingly, control outputs 1 and 2 cannot be used as output assign-
ments. Special output units are already set on position-proportional
type controllers.
•
On a position-proportional type controller, the following functions are
disabled:
MV limitter
P and PD control
40% AT
LBA
HBA
ON/OFF control
•
To change the travel time, either set in the “travel time” parameter
(option mode), or execute motor calibration in the “motor calibra-
tion” parameter (option mode).
•
Default is “30:30 seconds.”
•
The valve opening can be monitored when a potentiometer is con-
nected to the controller. However, be sure to execute motor calibra-
tion after connecting the potentiometer.
•
Open, closed or hold can be selected as output at reset or PV error. Set
these outputs in the “MV at reset” or “MV at PV error” parameters
(level 2 mode).
•
Set the dead band in the “position-proportional dead band” parame-
ter (level 1 mode). Default is “2.0:2.0%”.
•
Set the open/close hysteresis in the “open/close hysteresis” parameter
(level 2 mode).
Open/close hysteresis
Dead band
MV-Valve opening
100%
0
-100%
OFF
ON
J
Position-propor-
tional control
8
7
Open
6
5
Close
17
16
15
C
W
O
Potentiometer
F
Travel time
F
Valve opening
monitor
F
Manipulated vari-
able at reset/PV
error
F
Other functions
Summary of Contents for E5EK
Page 1: ...User s Manual Cat No H089 E1 02 Digital Controller Programmable Type...
Page 24: ...CHAPTER 1 INTRODUCTION 1 14...
Page 36: ...CHAPTER 2 PREPARATIONS 2 12...
Page 162: ...CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6 20...
Page 176: ...CHAPTER 7 CALIBRATION 7 14...
Page 193: ...SETTING LIST A 11...