![Omron E5EK User Manual Download Page 161](http://html1.mh-extra.com/html/omron/e5ek/e5ek_user-manual_742646161.webp)
6.6 Program Example
E5EK
6--19
J
Examples of use
•
Set the unit No. to “00”.
•
In the following examples, data is shown in individual blocks to make the exam-
ples easier to understand. However, when actually creating programs, do not leave
spaces between frame items. Also, response are displayed without spaces between
frame items.
F
Set the set point to “300.0”
•
Input data
@ 00 5 05 3000
300.0
Set point
Write parameter
•
Response
@ 00 5 05 00 3000 (FCS) *
Normal end
F
Start running
•
Input data
@ 00 3 00 0000
Run
Run/Reset
Special command
•
Response
@ 00 3 00 00 0000 (FCS) *
Normal end
F
Monitor process value
•
Input data
@ 00 1 00 0000
Dummy data
Monitor process value
Read parameter
•
Response
@ 00 1 00 00 2000 (FCS) *
Process value = 2000
Normal end
Summary of Contents for E5EK
Page 1: ...User s Manual Cat No H089 E1 02 Digital Controller Programmable Type...
Page 24: ...CHAPTER 1 INTRODUCTION 1 14...
Page 36: ...CHAPTER 2 PREPARATIONS 2 12...
Page 162: ...CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6 20...
Page 176: ...CHAPTER 7 CALIBRATION 7 14...
Page 193: ...SETTING LIST A 11...