E5EK
5--49
Transfer output type
Transfer output upper limit
Transfer output lower limit
Conditions of Use
The transfer output function must be in
use.
•
These parameters set the transfer output conditions.
•
The “transfer output type” parameter selects one of the following data items as
the transfer output type, and assigns this to transfer output:
Present SP, Process value, Manipulated variable (heat) (standard type), Manipu-
lated variable (cool) (during heating and cooling control on a standard type con-
troller), Valve opening (during position-proportional control)
•
The “transfer output upper limit” and “transfer output lower limit” parameters
are used for scaling of transfer output. The setting range varies according to this
output data. Also, a lower limit value larger than the upper limit value may be set.
•
Using temperature input, the decimal point position of the present SP or process
value is dependent on the currently selected sensor, and using analog input on the
results of scaling.
•
Set the scaling of the present SP or process value within the sensor input indica-
tion range.
Transfer Output Type
Transfer Output Lower Limit to
Transfer Output Upper Limit
“
” Present SP
-1999 to 9999
“
” Process Value
-1999 to 9999
“
” Manipulated variable (heat)
-5.0% to 105.0% (standard control), 0.0 to 105.0% (heat-
ing and cooling control)
“
” Manipulated variable (cool)
0.0 to 105.0%
“
” Valve opening
-10.0 to 110.0%
•
Default : [
].
F
Related description
4.11 How to Use Transfer Output (page 4-28)
F
Option units
E53-AKF
Option Mode
Function
Setting
See
Model
Summary of Contents for E5EK
Page 1: ...User s Manual Cat No H089 E1 02 Digital Controller Programmable Type...
Page 24: ...CHAPTER 1 INTRODUCTION 1 14...
Page 36: ...CHAPTER 2 PREPARATIONS 2 12...
Page 162: ...CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6 20...
Page 176: ...CHAPTER 7 CALIBRATION 7 14...
Page 193: ...SETTING LIST A 11...