CHAPTER 5 PARAMETERS
E5EK
5--22
Control period (heat)
Control period (cool)
Conditions of Use
Relay, SSR or voltage output must set
as the outputs, and the control must be
set to advanced PID control, standard
control or heating and cooling control.
•
Sets the pulse output period. Set the control period taking the control characteris-
tics and life expectancy of the controller into consideration.
•
In a standard control system, use the “control period (heat)” parameter. The “con-
trol period (cool)” parameter cannot be used.
•
In a heating and cooling control system, the control period can be set indepen-
dently for heating and cooling. Use the “control period (heat)” parameter to set
the heating side control period, and use the “control period (cool)” parameter to
set the cooling side control period.
Parameter
Setting Range
Unit
Default
Control period (heat)
1 to 99
Second
20
Control period (cool)
1 to 99
Second
20
F
Related description
3.3 Setting Output Specifications (page 3-7)
F
Related parameters
“Control output 1 assignment” “Control output 2 assignment” (setup mode)
E5EK-TAA2