CHAPTER 6 USING THE COMMUNICATIONS FUNCTION
E5EK
6--8
Parameter No.
Parameter
Data Setting and Monitor Range
Mode
00
PV monitor
*1 *2
Scaling lower limit -10% to scaling upper limit +10%
01
Set point
*1
Set point lower limit to set point upper limit
04
MV monitor (heat)
*1
-5.0 to 105.0
Level 0
42
MV monitor (cool)
*1
0.0 to 105.0
14
Valve opening monitor
*1
-10.0 to 110.0
02
Alarm value 1
-1999 to 9999
03
Alarm value 2
-1999 to 9999
Program
41
Alarm value 3
-1999 to 9999
g
19
Proportional band
0.1 to 999.9
20
Integral time
0 to 3999
21
Derivative time
0 to 3999
22
Cooling coefficient
0.01 to 99.99
09
Dead band
-19.99 to 99.99
87
Position-proportional dead
band
0.1 to 10.0
L
l
23
Manual reset value
0.0 to 100.0
Level 1
06
Hysteresis (heat)
0.01 to 99.99
43
Hysteresis (cool)
0.01 to 99.99
07
Control period (heat)
1 to 99
08
Control period (cool)
1 to 99
17
Heater current monitor *1
0.0 to 55.0
18
Heater burnout alarm
0.0 to 50.0
46
LBA detection time
0 to 9999
47
MV at reset
*6
-5.0 to 105.0
48
MV at PV error
*6
-5.0 to 105.0
50
MV upper limit
*3
MV lower limit +0.1 to 105.0
49
MV lower limit
*4
-5.0 to MV upper limit -0.1
51
MV change rate limit
0.0 to 100.0
56
Input digital filter
0 to 9999
Level 2
88
Open/close hysteresis
0.1 to 20.0
25
Alarm 1 hysteresis
0.01 to 99.99
26
Alarm 2 hysteresis
0.01 to 99.99
52
Alarm 3 hysteresis
0.01 to 99.99
53
Input shift upper limit
-199.9 to 999.9
54
Input shift lower limit
-199.9 to 999.9
*1 Possible only during reading
*2 During temperature input, the range becomes the range of use of the selected sensor.
*3 During heating and cooling control, the range becomes 0.0 to 105.0.
*4 During heating and cooling control, the range becomes -105.0 to 0.0.
*5 During position-proportional control, the range becomes 1 to 3999.
*6 During heating and cooling control, the range becomes -105.0 to 105.0.
During position-proportional control, you can select between 0: Hold/1: Open/2: Close. (Defaults is “0 : hold”.)
*3
*5
Summary of Contents for E5EK
Page 1: ...User s Manual Cat No H089 E1 02 Digital Controller Programmable Type...
Page 24: ...CHAPTER 1 INTRODUCTION 1 14...
Page 36: ...CHAPTER 2 PREPARATIONS 2 12...
Page 162: ...CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6 20...
Page 176: ...CHAPTER 7 CALIBRATION 7 14...
Page 193: ...SETTING LIST A 11...