CHAPTER 4 APPLIED OPERATION
E5EK
4--24
•
The heater burnout alarm function cannot be used when the heater is
controlled by a phase control system or by a cycle control system.
Also, the heater burnout alarm function cannot be applied on 3-phase
heaters.
To detect heater burnout on a 3-phase heater, use the K2CU-F
jj
A-
j
GS (with
gate input terminal). (For details, see the respective product catalog.)
•
Calculate the set value by the following formula:
Set value =
(current value at normal ope current value at burnout)
2
•
Set the current value at burnout when two or more heaters are con-
nected to the CT to the value at the time that the heater having the
smaller(est) current value burns out (the value when one of the heat-
ers burns out with all heaters at the same current).
•
Make sure that the following condition is satisfied:
Heater of current 10.0 A or less
Current value at normal operation - current value at heater
burnout
≧
1A
When resultant current is less than 1 A, detection is unstable.
Heater of current 10.0 A minimum
Current value at normal operation - current value at heater
burnout
≧
2.5 A
When resultant current is less than 2.5 A, detection is unstable.
•
The set value can be set within the range 0.1 to 49.9 A. Heater burn-
out is not detected when the setting is “0.0” or “50.0”. When the set-
ting is “0.0”, the heater burnout alarm is set to “OFF,” and when the
setting is “50.0”, the heater burnout alarm is set to “ON.”
•
Set the total current value at normal heater operation to 50 A or less.
When set to 55.0 A minimum, [
] is displayed in the “heater cur-
rent monitor” parameter.
J
How to calculate
the heater burn-
out set value
Summary of Contents for E5EK
Page 1: ...User s Manual Cat No H089 E1 02 Digital Controller Programmable Type...
Page 24: ...CHAPTER 1 INTRODUCTION 1 14...
Page 36: ...CHAPTER 2 PREPARATIONS 2 12...
Page 162: ...CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6 20...
Page 176: ...CHAPTER 7 CALIBRATION 7 14...
Page 193: ...SETTING LIST A 11...