APPENDIX
E5EK
A--2
SPECIFICATIONS
J
Ratings
Supply voltage
100 to 240V AC, 50/60 Hz
24 VAC/DC, 50/60 Hz
Operating Voltage
Range
85% to 110% of rated supply voltage
Power Consumption
15VA
12 VA, 8 W
Sensor Input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII *1, *2
Platinum resistance thermometer: JPt100, Pt100
Voltage input: 4 to 20 mA, 0 to 20 mA (input impedance 150
Ω
)
Current input: 1 to 5 V, 0 to 5 V, 0 to 10 V (input impedance 1M
Ω
)
Sub-Input
CT input: E54-CT1, E54-CT3
Potentiometer: 100
Ω
to 2.5 k
Ω
Control Output
According to output unit (see “Output Unit Ratings and Characteristics” (page A-4)
Auxiliary Output
SPST-NO, 3 A at 250 VAC (resistive load)
Control Method
Advanced PID or ON/OFF control
Setting Method
Digital setting using front panel keys.
Indication Method
7-segment digital display, bar graph and LEDs
Other Functions
According to option unit (see “Option Unit Ratings and Characteristics” (page A-4)
Ambient Temperature
-10
°
C to 55
°
C (without condensation and icing)/3-year warranty period: -10 to 50
°
C
Ambient Humidity
35% to 85% (relative humidity)
Storage Temperature
-25
°
C to 65
°
C (without condensation and icing)
*1 Thermocouple W is W/Re5-26.
*2 For the setting ranges and indication ranges for each of inputs, see page A-4.
*1, *2
Summary of Contents for E5EK
Page 1: ...User s Manual Cat No H089 E1 02 Digital Controller Programmable Type...
Page 24: ...CHAPTER 1 INTRODUCTION 1 14...
Page 36: ...CHAPTER 2 PREPARATIONS 2 12...
Page 162: ...CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6 20...
Page 176: ...CHAPTER 7 CALIBRATION 7 14...
Page 193: ...SETTING LIST A 11...