521
Auxiliary Area Allocations by Function
Appendix C
Clock
Clock Information
Note
The clock data is stored in the CPU Unit as BCD.
Operation Start and End Times
Option Board Error Flag
A315.13
ON when the Option Board is removed while the power is
being supplied.
CPU Unit operation will continue and the ERR/ALM indi-
cator will flash.
OFF when the error has been cleared.
Read-only
When an error
occurs
Flash Memory Error Flag
A315.15
ON when writing to the internal flash memory fails.
CPU Unit operation will continue and the ERR/ALM indi-
cator will flash.
OFF when the error has been cleared.
Read-only
When an error
occurs
Other Fatal Error Flag
A402.00
ON when a non-fatal error that is not defined for A402.01
to A402.15 occurs. Detailed information is output to the
bits of A314.
OFF: No other fatal error
ON: Other fatal error
Read-only
When an error
occurs
Name
Address
Description
Access
Updated
Clock Data
The clock data from the clock built into the CPU Unit is stored here in BCD.
Read-only
A351.00 to A351.07
Seconds: 00 to 59 (BCD)
A351.08 to A351.15
Minutes: 00 to 59 (BCD)
A352.00 to A352.07
Hour: 00 to 23 (BCD)
A352.08 to A352.15
Day of the month: 01 to 31 (BCD)
A353.00 to A353.07
Month: 01 to 12 (BCD)
A353.08 to A353.15
Year: 00 to 99 (BCD)
A354.00 to A354.07
Day of the week: 00: Sunday, 01: Monday, 02: Tuesday,
03: Wednesday, 04: Thursday, 05: Friday, 06: Saturday
Name
Address
Description
Access
Updated
Operation Start Time
A515 to
A517
The time that operation started as a result of changing
the operating mode to RUN or MONITOR mode is stored
here in BCD.
A515.00 to A515.07: Seconds (00 to 59)
A515.08 to A515.15: Minutes (00 to 59)
A516.00 to A516.07: Hour (00 to 23)
A516.08 to A516.15: Day of month (01 to 31)
A517.00 to A517.07: Month (01 to 12)
A517.08 to A517.15: Year (00 to 99)
Note
The previous start time is stored after turning ON
the power supply until operation is started.
Read/write
Operation End Time
A518 to
A520
The time that operation stopped as a result of changing
the operating mode to PROGRAM mode is stored here in
BCD.
A518.00 to A518.07: Seconds (00 to 59)
A518.08 to A518.15: Minutes (01 to 59)
A519.00 to A519.07: Hour (00 to 23)
A519.08 to A519.15: Day of month (01 to 31)
A520.00 to A520.07: Month (01 to 12)
A520.08 to A520.15: Year (00 to 99)
Note
If an error occurs in operation, the time of the
error will be stored. If the operating mode is then
changed to PROGRAM mode, the time that PRO-
GRAM mode was entered will be stored.
Read/write
Name
Address
Description
Access
Updated
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...