266
Inverter Positioning
Section 5-3
Low-speed Operation
Using Minimum Output
Setting
An inductive motor driven with an inverter is different from a servomotor in that
the torque at low speeds is so low that it may not be possible to turn the motor
shaft at the minimum frequency. The CP1L provide a minimum output setting
the ensure a minimum output to enable positioning at low speeds even when
there are extremely few pulses in the error counter.
Absolute Positioning
The amount of movement (i.e., amount of rotation) is input to the high-speed
counter as feedback pulses. During inverter positioning, the present value of
the high-speed counter can be used as an absolute position.
Note
The absolute position will change if the present value of the high-speed
counter is changed or the high-speed counter is reset.
5-3-4
Specifications
Inverter Positioning
Specifications
Pulse frequency
Time
In-position width
Pulse Output Flag
In-position flag
PLS2
instruction
Error counter
present value
Error counter
error setting
Error Counter Error
Flag (Output value cleared.)
Error Counter Reset Bit
(Error counter cleared.)
Motor shaft
turned manually.
Error counter
error occurs.
Item
Specification
Applicable inverters
Inverter that receives frequency commands from an analog
input or via Modbus-RTU communications. (Control method:
V/f control, vector control, etc.)
Applicable motors
Depends on the inverter (e.g., squirrel-cage inductive motor)
Number of position-
ing ports and
response frequency
Two ports at 100 kHz (within the speed command range of the
pulse output instructions)
Inverter command
output method
Modbus-RTU communications commands or analog output
(from ladder program)
Present value coor-
dinate system
With origin: Absolute coordinate system
Without origin: Relative coordinate system
Present value range
32 bits: 8000 000 to 7FFF FFFF hex (range of position com-
mand values and present values for pulse output instructions)
Output modes
Continuous output (Number of pulses not specified.)
Independent mode (Number of pulses specified.)
Acceleration/decel-
eration control
Trapezoidal or S-curve acceleration/deceleration
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...