![background image](http://html1.mh-extra.com/html/omron/cp1l-l14d-series/cp1l-l14d-series_operation-manual_742090174.webp)
141
Timers and Counters
Section 4-9
The refresh method for counter PVs can be set from the CX-Programmer to
either BCD or binary. (Refer to the previous page).
It is not recommended to use the same counter number in two counter
instructions because the counters will not operate correctly if they are count-
ing simultaneously. If two or more counter instructions use the same counter
number, an error will be generated during the program check, but the counters
will operate as long as the instructions are not executed in the same cycle.
The following table shows when counter PVs and Completion Flags will be
reset.
Forcing Bit Status
Counter Completion Flags can be force-set and force-reset.
Counter PVs cannot be force-set or force-reset, although the PVs can be
refreshed indirectly by force-setting/resetting the Completion Flag.
Restrictions
There are no restrictions in the order of using counter numbers or in the num-
ber of N.C. or N.O. conditions that can be programmed. Counter PVs can be
read as word data and used in programming.
Instruction name
Effect on PV and Completion Flag
Reset
Mode
change
PLC startup
Reset Input
CNR(545)/CN
RX(547)
Interlocks
(IL-ILC)
COUNTER:
CNT/CNTX(546)
PV
→
0
Flag
→
OFF
Maintained
Maintained
Reset
Reset
Maintained
REVERSIBLE
COUNTER:
CNTR(012)/CNTRX(548)
COUNTER WAIT:
CNTW(814)/CNTWX(818)
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...