284
Inverter Positioning
Section 5-3
Refer to
7-3 Analog Output Units
for operating procedures for the Analog Out-
put Unit.
■
Calculation Example
Conditions
Inverter’s maximum output frequency: 60 Hz
Calculation
The stored analog output value is calculated as follows:
Stored analog
output value
Inverter frequency
command value (Hz)
Inverter's max. output frequency (Hz)
6,000
CP1L
Automatic
calculations
Inverter
frequency
command value
Auxiliary Area
A23/A33
6,000
Inverter maximum
output frequency (Hz)
Stored analog
output value
Analog output
Unit: 0.01 Hz
1
100
Converting values in A23/A33 to Hz.
Converted in ladder program
Stored analog
output value
60
6,000
1
Auxiliary Area
A23/A33
(Unit: 0.01 Hz)
Auxiliary Area
A23/A33
(Unit: 0.01 Hz)
100
1
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...