570
Auxiliary Area Allocations by Address
Appendix D
A641
A641.00 Serial Port 1
Modbus-
RTU Master
Execution
Bit (CP1L
M-type CPU
Units)
Turn ON this bit to send a command
and receive a response for serial port
1 of a CP1L M-type CPU Unit using
the Modbus-RTU easy master func-
tion.
This bit will be turned OFF automati-
cally by the system when communi-
cations have been completed.
Turned ON:
Execution
started
ON: Execution
in progress.
OFF: Not exe-
cuted or execu-
tion completed.
Retained
Cleared
---
DM fixed
allocation
words for
Modbus-
RTU Easy
Master:
D32200 to
D32299
A641.01 Serial Port 1
Modbus-
RTU Master
Execution
Normal Flag
(CP1L M-
type CPU
Units)
ON when one command has been
sent and the response received for
serial port 1 of a CP1L M-type CPU
Unit using the Modbus-RTU easy
master function.
ON: Execution
normal.
OFF: Execution
error or still in
progress.
Retained
Cleared
---
A641.02 Serial Port 1
Modbus-
RTU Master
Execution
Error Flag
(CP1L M-
type CPU
Units)
ON when an error has occurred in
communications for serial port 1 of a
CP1L M-type CPU Unit using the
Modbus-RTU easy master function.
The error code is output to D32352
in the DM fixed allocation words for
Modbus-RTU Easy Master.
ON: Execution
error.
OFF: Execution
normal or still
in progress.
Retained
Cleared
---
A642
All
Analog
Adjustment
PV
Stores the value set on the analog
adjuster as a hexadecimal value
(resolution: 1/256).
0000 to 00FF
hex
Retained
Cleared
---
---
A643
All
External
Analog Set-
ting Input
PV
Stores the value set from the exter-
nal analog setting input as a hexa-
decimal value (resolution: 1/256).
0000 to 00FF
hex
Retained
Cleared
---
---
A720 to
A722
All
Power ON
Clock Data 1
These words contain the time at
which the power was turned ON one
time before the startup time stored in
words A510 to A511.
A720.00 to A720.07: Seconds (00 to
59)
A720.08 to A720.15: Minutes (00 to
59)
A721.00 to A721.07: Hour (00 to 23)
A721.08 to A721.15: Day of month
(00 to 31)
A722.00 to A722.07: Month (01 to
12)
A722.08 to A722.15: Year (00 to 99)
See at left.
Retained
Retained
Written
when
power is
turned
ON.
A723 to
A725
All
Power ON
Clock Data 2
These words contain the time at
which the power was turned ON two
times before the startup time stored
in words A510 to A511.
A723.00 to A723.07: Seconds (00 to
59)
A723.08 to A723.15: Minutes (00 to
59)
A724.00 to A724.07: Hour (00 to 23)
A724.08 to A724.15: Day of month
(00 to 31)
A725.00 to A725.07: Month (01 to
12)
A725.08 to A725.15: Year (00 to 99)
See at left.
Retained
Retained
Written
when
power is
turned
ON.
A726 to
A728
All
Power ON
Clock Data 3
These words contain the time at
which the power was turned ON
three times before the startup time
stored in words A510 to A511.
A726.00 to A726.07: Seconds (00 to
59)
A726.08 to A726.15: Minutes (00 to
59)
A727.00 to A727.07: Hour (00 to 23)
A727.08 to A727.15: Day of month
(00 to 31)
A728.00 to A728.07: Month (01 to
12)
A728.08 to A728.15: Year (00 to 99)
See at left.
Retained
Retained
Written
when
power is
turned
ON.
Addresses
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
Flags,
Settings
Word
Bits
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...