105
Wiring CP1L CPU Units
Section 3-4
3-4-3
Wiring Safety and Noise Controls
I/O Signal Wiring
Whenever possible, place I/O signal lines and power lines in separate ducts or
conduits both inside and outside of the control panel.
If the I/O wiring and power wiring must be routed in the same duct, use
shielded cables and connect the shields to the GR terminal to reduce noise.
Inductive Loads
When an inductive load is connected to an I/O Unit, connect a surge suppres-
sor or diode in parallel with the load as shown below.
Note
Use surge suppressors and diodes with the following specifications.
OUT
R
COM
L
+
OUT
R
COM
L
+
SYSMAC CP1L
SYSMAC CP1L
Example Method 1
Example Method 2
Use a dark current of approximately 1/3 the rated current of the incandescent lamp.
Install a limit resistance.
(1)
(2)
(1)
(2)
(1)
(2)
Suspended duct
In-floor duct
(1) = I/O cables
(2) = Power cables
Conduits
L
IN
COM
OUT
COM
OUT
COM
L
+
Diode
DC input
Relay output
Surge suppressor
Relay output or
transistor output
Diode
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...