424
Analog I/O Units
Section 7-4
Setting D/A Conversion Data
Output data is written to the Analog I/O Unit’s allocated output word, word
n+1.
Note
Word (n + 1) can be used for either the range code or the analog output set
value.
1,2,3...
1.
The set value range is 0000 to 00FF hex when the output signal range is 0
to 10 V/4 to 20 mA.
2.
The set value range is divided into two parts: 8000 to 80FF hex (
−
10 to 0
V) and 0000 to 00FF hex (0 to 10 V) when the output signal range is
−
10
to 10 V.
3.
If FF
@@
is input, 0 V/4 mA will be output.
4.
If an output value is specified, the following bits will be ignored.
• Output range of
−
10 to 10 V: Bits 08 to 14
• Output range of 0 to 10 V/4 to 20 mA: Bits 08 to 15
Startup Operation
After power is turned ON, it will require two cycle times plus approx. 100 ms
before the first data is converted. The following instructions can be placed at
the beginning of the program to delay reading converted data from analog
inputs until conversion is actually possible.
Analog input data will be 0000 until initial processing has been completed.
Analog output data will be 0 V or 0 mA until the range code has been written.
After the range code has been written, the analog output data will be 0 V or
4 mA if the range is 0 to 10 V,
−
10 to 10 V, or 4 to 20 mA.
MOV(21)
MOVE instruction
Ladder program
Word n + 1
CPU Unit
Analog I/O Unit
(See note.)
•
Writes the range code
•
Writes the set value
Range code
Analog output set value
"n" is the last output word allocated to the CPU
Unit, or previous Expansion Unit or Expansion I/O
Unit.
Analog devices
•
Adjustment equipment
•
Servo Controller
•
Variable speed device
•
Recorder
•
Other
n + 1
15
00
Sign bit
(Used when the
output signal range is
−
10 to 10 V.)
Set value (00 to FF hex)
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...