210
Pulse Outputs
Section 5-2
Specifying the Origin
Search Direction (CW or
CCW Direction)
Sets the direction to move when detecting the Origin Input Signal.
Typically, the origin search is performed so that the Origin Input Signal's rising
edge is detected when moving in the origin search direction.
Origin Search Speed
These are the motor speed settings used in the origin search.
Note
The origin search will not be performed in these cases:
Origin search high speed
≤
Origin search proximity speed
Origin search proximity speed
≤
Origin search initial speed
Origin Search/Return Initial Speed
Sets the motor's starting speed when the origin search is executed. Specify
the speed in the number of pulses per second (pps).
Origin Search High Speed
Sets the motor's target speed when the origin search is executed. Specify the
speed in the number of pulses per second (pps).
Origin Search Proximity Speed
Sets the motor's speed after the Origin Proximity Input Signal is detected.
Specify the speed in the number of pulses per second (pps).
Origin Search Acceleration Rate
Sets the motor's acceleration rate when the origin search is executed. Specify
the amount to increase the speed (Hz) per 4-ms interval.
Origin Search Deceleration Rate
Sets the motor's acceleration rate when the origin search function is deceler-
ating. Specify the amount to decrease the speed (Hz) per 4-ms interval.
Origin Compensation
After the origin has been determined, the origin compensation can be set to
compensate for a shift in the Proximity Sensor's ON position, motor replace-
ment, or other change.
2: Origin Proximity Input
Signal not used.
Note
When the limit input signal is received, the motor stops without deceleration.
Origin search
operation
Origin detection
method
1: Reversal mode 2
1
0
CCW
CCW
CCW
CW
CW
CW
Origin Input
Signal
Pulse output
Proximity speed for origin search
Start
Stop
CW limit input signal (See note.)
Start
Stop
Start
Limit stop (error code 0201)
Setting
Description
0
CW direction
1
CCW direction
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...