Analog I/O Units
Section 7-4
0 to 20 mA
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
current range of 0 to 20 mA. The entire output range is 0 to 21 mA.
4 to 20 mA
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
current range of 4 to 20 mA. The entire output range is 3.2 to 20.8 mA.
Averaging Function for
Analog Inputs
The averaging function can be enabled for inputs using the DIP switch. The
averaging function stores the average (a moving average) of the last eight
input values as the converted value. Use this function to smooth inputs that
vary at a short interval.
Open-circuit Detection
Function for Analog
Inputs
The open-circuit detection function is activated when the input range is set to
1 to 5 V and the voltage drops below 0.8 V, or when the input range is set to 4
to 20 mA and the current drops below 3.2 mA. When the open-circuit detec-
tion function is activated, the converted data will be set to 8,000.
The time for enabling or clearing the open-circuit detection function is the
same as the time for converting the data. If the input returns to the convertible
range, the open-circuit detection is cleared automatically and the output
returns to the normal range.
0 mA
20 mA
21 mA
0000 (0)
189C
(6300)
1770
(6000)
7FFF
8000
Conversion Data
Hexadecimal (Decimal)
4 mA
20 mA
20.8 mA
3.2 mA
189C
(6300)
1770
(6000)
0 mA
7FFF
FED4
(
−
300)
8000
Conversion Data
Hexadecimal (Decimal)
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...