133
I/O Area and I/O Allocations
Section 4-2
Example 2: Connecting Expansion I/O Units with Only Inputs or Only
Outputs
If Expansion I/O Units with only inputs or only outputs are connected, the
input or output word not used by an Expansion I/O Unit is allocated to the next
Unit that requires it.
24 input points
16 output points
24 input points
16 output points
15 14 13 12 11 10
09
08 07
06 05 04 03 02 01 00
CIO 0
CIO 1
CIO 2
CIO 3
CIO 4
CIO 5
CIO 6
CIO 7
Do not use.
Can be used as work bits.
CIO 0.00 to CIO 0.11
CIO 1.00 to CIO 1.11
CIO 2.00 to CIO 2.11
CIO 3.00 to CIO 3.11
CIO 4.00 to CIO 4.11
CIO 5.00 to CIO 5.11
CIO 6.00 to CIO 6.11
CIO 7.00 to CIO 7.11
CIO 106.00 to CIO 106.07
CIO 107.00 to CIO 107.07
CIO 104.00 to CIO 106.07
CIO 105.00 to CIO 105.07
24 input points
24 input points
16 output points
16 output points
CIO 102.00 to CIO 102.07
CIO 103.00 to CIO 103.07
CIO 100.00 to CIO 100.07
CIO 101.00 to CIO 101.07
CPU Unit
(40 I/O points)
Three Expansion I/O Units, each with 40 I/O points
CPU Unit with 40 I/O points
First Expansion I/O Unit with 40 I/O points
Second Expansion I/O Unit with 40 I/O points
Third Expansion I/O Unit with 40 I/O points
CPU Unit with 40 I/O points
First Expansion I/O Unit with 40 I/O points
Second Expansion I/O Unit with 40 I/O points
Third Expansion I/O Unit with 40 I/O points
CIO 100
CIO 101
CIO 102
CIO 103
CIO 104
CIO 105
CIO 106
CIO 107
Input bits
Input bits
Output bits
Output bits
Bit
104.00
104.07
Bit
15 14 13 12
11 10 09 08 07 06
05 04 03 02 01 00
CIO 0
CIO 1
CIO 2
CIO 3
CIO 100
CIO 101
CIO 102
CIO 103
CIO 104
Do not use.
Can be used as work bits.
18 input points
12 output points
CPU Unit
(30 I/O points)
8 input points
CIO 0.00 to CIO 0.11
CIO 1.00 to CIO 1.05
CIO 100.00 to CIO 100.07
CIO 101.00 to CIO 101.03
CIO 2.00 to CIO 2.07
CIO 102.00 to CIO 102.07
CIO 103.00 to CIO 103.07
No outputs
16 output points
No inputs
12 input points
8 output points
CIO 3.00 to CIO 3.11
CIO 104.00 to CIO 104.07
First Expansion I/O Unit:
Unit with 8 inputs
Second Expansion I/O Unit:
Unit with 16 outputs
Third Expansion I/O Unit:
Unit with 20 I/O
CPU Unit with 30 I/O points
First Expansion I/O Unit: Unit with 8 inputs
Third Expansion I/O Unit: Unit with 20 I/O
CPU Unit with 30 I/O
points
Second Expansion I/O Unit:
Unit with 16 outputs
Third Expansion I/O Unit: Unit with 20 I/O
Input bits
Input bits
Output bits
Output bits
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...