186
Pulse Outputs
Section 5-2
Reset Bits
The pulse output PV will be cleared when this bit is
turned from OFF to ON.
0: Not cleared.
1: Clear PV.
A540.00
A541.00
CW Limit Input Signal Flags
This is the CW limit input signal, which is used in the
origin search.
ON when turned ON from an external
input.
A540.08
A541.08
CCW Limit Input Signal Flags
This is the CCW limit input signal, which is used in
the origin search.
ON when turned ON from an external
input.
A540.09
A541.09
Positioning completed input signals
This is the positioning completed input signal, which
is used in the origin search.
ON when turned ON from an external
input.
A540.10
A541.10
Accel/Decel Flags
ON when pulses are being output according to an
ACC(888) or PLS2(887) instruction and the output
frequency is being changed in steps (accelerating or
decelerating).
0: Constant speed
1: Accelerating or decelerating
A280.00
A281.00
Overflow/Underflow Flags
ON when an overflow or underflow has occurred in
the pulse output PV.
0: Normal
1: Overflow or underflow
A280.01
A281.01
Output Amount Set Flags
ON when the number of output pulses has been set
with the PULS instruction.
0: No setting
1: Setting made
A280.02
A281.02
Output Completed Flags
ON when the number of output pulses set with the
PULS(886)/PLS2(887) instruction has been output.
0: Output not completed.
1: Output completed.
A280.03
A281.03
Output In-progress Flags
ON when pulses are being output from the pulse
output.
0: Stopped
1: Outputting pulses.
A280.04
A281.04
No-origin Flags
ON when the origin has not been determined for the
pulse output.
0: Origin established.
1: Origin not established.
A280.05
A281.05
At-origin Flags
ON when the pulse output PV matches the origin
(0).
0: Not stopped at origin.
1: Stopped at origin.
A280.06
A281.06
Output Stopped Error Flags
ON when an error occurred while outputting pulses
in the origin search function.
0: No error
1: Stop error occurred.
A280.07
A281.07
Stop Error Codes
When a Pulse Output Stop Error occurs, the error
code is stored in that pulse outputs corresponding
Stop Error Code word.
---
A444
A445
Function
Pulse output number
0
1
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...