374
Memory Cassette Functions
Section 6-6
b.
Select the
Data Memory
Option in the
Backup to Flash Memory
Area
and click the
Backup
Button.
The DM data will be written to the built-in flash memory.
Note
The DM data that is saved and written at startup is the entire DM Area (D0 to
D32767).
PLC Setup
1,2,3...
1.
Set
Do not detect Low Battery (run without battery)
to
Do not detect
.
2.
Set
IOM Hold Bit Status at Startup
and
Forced Status Hold Bit Status at
Startup
to
Clear (OFF)
.
3.
Set
Read DM from flash memory
to
Read
. (Only when DM initial values
have been saved as described above.)
!Caution
The CP1L CPU Units automatically back up the user program and parameter
data to flash memory when these are written to the CPU Unit. Also, the CX-
Programmer can be used to save all of the data in the DM Area to the flash
memory for use as initial values when the power supply is turned ON. Neither
of these functions saves the I/O memory data (including HR Area data,
counter PVs and Completion Flags, and DM Area data other than initial val-
ues). The HR Area data, counter PVs and Completion Flags, and DM Area
data other than initial values are held during power interruptions with a bat-
tery. If there is a battery error, the contents of these areas may not be accu-
rate after a power interruption. If HR Area data, counter PVs and Completion
Flags, and DM Area data other than initial values are used to control external
outputs, prevent inappropriate outputs from being made whenever the Battery
Error Flag (A402.04) is ON.
6-6
Memory Cassette Functions
6-6-1
Overview
CP1L CPU Units have Memory Cassette functions that enable data in the
CPU Unit to be stored on and read from a special CP1W-ME05M Memory
Cassette. These functions can be used for the following applications.
• Copying data to other CPU Units to produce duplicate devices.
• Backing up data in case the CPU Unit needs to be replaced due to any
malfunction.
• Writing and updating data when existing device versions are upgraded.
Memory Cassette
Specifications
Use the following Memory Cassette.
Model
Specifications
CP1W-ME05M
• Memory size
512 Kwords
• Storage capacity The following CPU Unit data (for each Unit)
• User programs
• Parameters
• Comment memory
• Function Block (FB) sources
• DM initial values in the built-in flash memory
• DM in RAM
• Write method
Operations from the CX-Programmer
• Read method
Powering up with DIP switch pin SW2 set to
ON, or operations from the CX-Programmer
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...