36
Part Names and Functions
Section 2-1
Note
The following data will be write-protected if pin SW1 is turned ON:
• The entire user program (all tasks)
• All data in parameter areas (such as the PLC Setup)
When SW1 is turned ON, the user program and the data in the pa-
rameter areas will not be cleared even if the All Clear operation is
performed from a Peripheral Device (i.e., the CX-Programmer).
(7)
Memory Cassette Slot
Used for mounting a CP1W-ME05M Memory Cassette. When mounting
a Memory Cassette, remove the dummy cassette.
Data, such as CP1L CPU Unit programs, parameters, and data memory,
can be transferred to the Memory Cassette to be saved.
(8)
Power Supply, Ground, and Input Terminal Block
(9)
Option Board Slots
The following Option Boards can be mounted in either slot 1 or slot 2.
• CP1W-CIF01 RS-232C Option Board
• CP1W-CIF11 RS-422A/485 Option Board
!Caution
Always turn OFF the power supply to the PLC before mounting or removing
an Option Board.
(10) Input Indicators
The input indicators light when input terminal contacts turn ON.
SW2
ON
Data automatically
transferred from
Memory Cassette at
startup.
Used to enable pro-
grams, Data Memory, or
parameters saved on a
Memory Cassette to be
opened by the CPU Unit
at startup.
OFF
OFF
Data not transferred.
SW3
ON
A395.12 ON
This pin enables control-
ling a bit in memory with-
out using an input relay.
OFF
OFF
A395.12 OFF
SW4
ON
Used for peripheral
bus.
Used to enable a Serial
Communications Option
Board mounted in Option
Board Slot 1 to be used
by the peripheral bus.
OFF
OFF
According to PLC
Setup.
Power supply ter-
minals
Used to provide a 100- to 240-VAC or 24-VDC power
supply.
Ground terminals
Functional ground (
):
Connect this ground to strengthen noise immunity and to
prevent electric shock.
(AC power supply models only.)
Protective ground (
):
To prevent electric shock, ground to 100
Ω
or less.
Input terminals
Used to connect input devices.
No.
Setting
Description
Application
Default
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...