389
Program Protection
Section 6-7
Write-protection
Using Passwords
The program (or selected tasks) can also be write-protected if the write pro-
tection option is selected from the CX-Programmer when a password is being
registered for the entire program or those selected tasks. The write protection
setting can prevent unauthorized or accidental overwriting of the program.
Note
1.
If the selected tasks are write-protected by selecting this option when reg-
istering a password, only the tasks (program) that are password-protected
will be protected from overwriting. It will still be possible to overwrite other
tasks with operations such as online editing and task downloading.
2.
All tasks (programs) can be overwritten when program read protection is
not enabled.
Operating Procedure
1,2,3...
Table 1 When registering a password in the
UM read protection password
Box or
Task read protection
Box, select the
Prohibit from overwriting to a protected
program
Option.
3.
Either select
PLC - Transfer - To PLC
to transfer the program or select
PLC - Protection - Set Password
and click the
OK
button.
Note
The setting to enable/disable creating file memory program files will not take
effect unless the program is transferred to the CPU Unit. Always transfer the
program after changing this setting.
CX-Programmer
Password?
When a password is being registered for the entire user
program or selected tasks, program write-protection can be
enabled/disabled with an option setting.
The user program cannot be overwritten.
CPU Unit
Overwriting can be prohibited with password protection,
regardless of the DIP switch setting.
Memory Cassette
The user program cannot be overwritten.
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...