458
CompoBus/S I/O Link Units
Section 7-6
The input word (m+1) contains the 8 bits of data from the Master Unit and two
CompoBus/S communications flags.
Write the data to be transmitted to the Master Unit in the output word (n+1).
Note
(1) The 8 bits of I/O data are not always transmitted simultaneously. In other
words, 8 bits of data transmitted from the Master CPU Unit at the same
time will not always reach the Slave CPU Unit simultaneously, and 8 bits
of data transmitted from the Slave CPU Unit at the same time will not al-
ways reach the Master CPU Unit simultaneously.
When the 8 bits of input data must be read together, modify the ladder
program in the CPU Unit receiving the data. For example, read the input
data twice in succession and accept the data only when the two values
match.
(2) Unused bits in the CompoBus/S I/O Link Unit’s output word can be used
as work bits, but unused bits in the output slaves cannot be used as work
bits.
(3) Unused bits in input word cannot be used as work bits.
Determining the Node
Number and Making DIP
Switch Settings
Node Number
• The CompoBus/S I/O Link Unit is a Slave Unit with 8 input bits and 8 out-
put bits. The node number setting is made using the DIP switch; the
inputs and outputs share the same node number.
• The range of possible node number settings is determined by the type of
PLC the Master Unit is mounted to and the settings on the Master Unit.
For details refer to the
CompoBus/S Operation Manual
.
Word m+1
15
00
07
08
09
CompoBus/S Communications Error Flag
0: Normal; 1: Error
CompoBus/S Communication Status Flag
0: Stopped; 1: Communicating
Data from the Master Unit
Word n+1
15
00
07
Data to be transferred to the Master Unit
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...