(11) Expansion I/O Unit Connector
CP-series Expansion I/O Units and Expansion Units (Analog I/O Units,
Temperature Sensor Units, CompoBus/S I/O Link Units, or DeviceNet I/O
Link Units) can be connected. Up to three Expansion Units or Expansion
I/O Units can be connected to a CPU Unit with 30 or 40 I/O points and
one Expansion Unit or Expansion I/O Unit can be connected to a CPU
Unit with 20 or 14 I/O points. (For details on using Expansion Units and
Expansion I/O Units, refer to
SECTION 7 Using Expansion Units and
Expansion I/O Units
.)
(12) Output Indicators
The output indicators light when output terminal contacts turn ON.
(13) External Power Supply and Output Terminal Block
2-1-2
CP1W-CIF01 RS-232C Option Boards
An RS-232C Option Board can be mounted to an Option Board slot on the
CPU Unit. With a CPU Unit with 30 or 40 I/O points, either Option Board slot
may be used.
When mounting an Option Board, first remove the slot cover. Grasp both of
the cover's up/down lock levers at the same time to unlock the cover, and then
pull the cover out.
Then to mount the Option Board, check the alignment and firmly press it in
until it snaps into place.
!Caution
Always turn OFF the power supply to the PLC before mounting or removing
an Option Board.
External power
supply terminals
CPU Units with AC power supply specifications have
external 24-VDC, 300-mA, power supply terminals.
(except for the CP1L-L
@
DR-A, which has a 200-mA
power supply terminals). They can be used as service
power supplies for input devices.
Output terminals
Used for connecting output devices.
COMM
Front
Back
(1) Communications Status Indicator
(2) RS-232 Connector
(3) CPU Unit Connector
Summary of Contents for CP1L-L14D Series
Page 2: ...CP1L L14D CP1L L20D CP1L M30D CP1L M40D CP1L CPU Unit Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 153: ...120 CP CPM1A series Expansion I O Unit Wiring Section 3 6...
Page 523: ...490 Troubleshooting Unit Errors Section 9 4...
Page 531: ...498 Replacing User serviceable Parts Section 10 2...
Page 563: ...530 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...578 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...605 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...606 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...636 Index...
Page 671: ...638 Revision History...