Instruction manual
NivuFlow Mobile 600
page 84
rev. 00 / 04.09.2017
•
External Reading
Possibly linearised measurement values available at the analog input are available
here.
Selection/Input Options:
Analog input:
>Input 1< or >Input 2< or >Input 3<
Output range:
>0-5 V< or >0-10V<
Value at 10 V:
manual input
Value at error:
>0 V< or >Hold value< or >10 V<
•
Path Velocity
If more than one flow velocity sensor is used and if the average flow velocity of the
individual measurement paths is to be determined it is possible to select the desired
flow velocity sensor and to output the according measurement value.
Selection/Input Options:
v-Path:
>Path 1< or >Path 2< depending on the number of connected
paths
Output range:
>0-5 V< or >0-10 V<
Value at 0 V:
manual input
Value at 10 V:
manual input
Value at error:
>0 V< or >Hold value< or >10 V<
28.3.3 Digital Inputs
The transmitter is equipped with one digital input.
Factory default:
Input not active
The following different functions can be assigned to the digital input.
Fig. 28-10 Digital input activation
•
Run Times
The system detects and saves the duration of the ongoing signal at the digital input.
Such records are used to gather information e. g. on pump run times or other equip-
ment run times.
Selection/Input Options:
Logic:
>not inverted< or >inverted<