60
Function list
Input/Output Group
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
I61
A43D
[Baud rate]
0 - 4
Select the Baud rate of the RS485.
3
O
0
1200 [bps]
1
2400 [bps]
2
4800 [bps]
3
9600 [bps]
4
19200 [bps]
I62
A43E
[Drive mode
select after
loss of
frequency
command]
0 - 3
It is used when freq command is given
via V1 /I terminal or RS485.
0
O
0
Continuous operation at the
frequency before its command is
lost.
1
Free Run stop (Output cut-off)
2
Decel to stop
3
Lost Preset
I63
A43F
[Wait time after
loss of
frequency
command]
0.1 -
120
[sec]
This is the time inverter determines
whether there is the input frequency
command or not. If there is no frequency
command input during this time, inverter
starts operation via the mode selected at
I62.
1.0
O
I64
A440
[Communi-
cation time
setting]
2 - 100
[ms]
Frame communication time
5
O
-
I65
A441
[Parity/stop bit
setting]
0-3
When the protocol is set, the
communication format can be set.
O
O
-
0
Parity: None, Stop Bit: 1
1
Parity: None, Stop Bit: 2
2
Parity: Even, Stop Bit: 1
3
Parity: Odd, Stop Bit: 1
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...