58
Function list
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
default
Adj.
during
run
Page
1
Output current 150 %
2
Output
voltage
AC 282V AC 564V
3
Inverter DC
link voltage
DC 400V DC 800V
I51
A433
[Analog output
level
adjustment]
10-
200
[%]
Based on 10V.
100
O
I52
A434
[Frequency
detection level]
0 - 400
[Hz]
Used when I54 or I55 is set to 0-4.
Cannot be set higher than F21.
30.00
O
I53
A435
[Frequency
detection
bandwidth]
10.00
O
I54
A436
[Multi-function
realy1 select]
0 - 27
0
FDT-1
17
O
1
FDT-2
2
FDT-3
3
FDT-4
I55
A437
[Multi-function
relay 2select]
4
FDT-5
12
O
5
Overload (OLt)
6
Inverter Overload (IOLt)
7
Motor stall (STALL)
8
Over voltage trip (Ovt)
9
Low voltage trip (Lvt)
10 Inverter Overheat (OHt)
11 Command loss
12 During Run
13 During Stop
14 During constant run
15 During speed searching
16 Wait time for run signal input
17 Fault Output
18 Warning for cooling fan trip
19 On Off Control
20 Pipe Broken
21 Over Pressure
22 Under Load Trip
23 Broken Belt Trip
24 Motor Alternation
25 MMC1
26 MMC2
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...