93
Basic Functions
B
as
ic
Fu
nc
tio
ns
7.7 Frequency limit
Frequency limit using Max Frequency and Start
7.7.1
Frequency
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function group 1
F21
[Max frequency]
-
40 - 400
50.00
Hz
F23
[Start frequency]
-
0.1 - 10
0.50
Hz
Max Frequency: Frequency highest limit. Any frequency cannot be set above [Max
frequency] except for F22 [Base frequency].
Start Frequency: Frequency lowest limit. If a frequency is set lower than this, 0.00 is
automatically set.
Frequency command limit using High/Low limit
7.7.2
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function group 1
F24
[Frequency high/low
limit select]
1
0 - 1
0
F25
[Frequency high
limit]
-
0 - 400
50.00
Hz
F26
[Frequency low limit] -
0 - 400
0.50
Hz
Set F24 to 1.
Active run frequency can be set within the range of F25 and F26.
►
When frequency setting is done via Analog input (voltage or current input), the inverter
operates within the range of high and low limit frequency as shown below.
►
This setting is also valid when frequency setting is done via keypad.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...