89
Basic Functions
B
as
ic
Fu
nc
tio
ns
High starting torque pattern
7.5.3
Group
Code
Parameter Name
Setting
Range
Default Unit
Function group 1
F30
[V/F pattern]
3, 4
0 - 4
0
Set F30 to {3 High starting torque 1} or {4 High starting torque 2}.
iG5H offers a Two types of high starting torque pattern suitable for special pump load
requiring high starting torque.
Otherwise Select high starting torque when: Wiring between the drive and motor
exceeds 150 m, An AC reactor is installed.
User V/F pattern operation
7.5.4
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 1
F30
[V/F pattern]
2
0 - 4
0
F31
[User V/F frequency 1]
-
0 - 400
15.00
Hz
-
-
F38
[User V/F voltage 4]
-
0 - 100
100
%
Select F30 to 2 {User V/F}.
User can adjust the Volt/Frequency ratio according to V/F pattern of specialized motors
and load characteristics.
In case of using a standard induction motor, if this value is set much higher than linear V/F
pattern, it could result in torque shortage or motor overheating due to over-energizing.
When User V/F pattern is active, F28 - [Torque Boost in forward direction] and F29 - [Torque
Boost in reverse direction] are deactivated.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...