Basic Functions
86
Accel/Decel pattern setting
7.4.4
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 1
F 2
[Accel pattern]
0
Linear
0
F 3
[Decel pattern]
1
S-curve
Function
group 2
H17
[S-Curve Accel/Decel start
side]
0-
100
40
%
H18
[S-Curve Accel/Decel end
side]
40
%
Accel/Decel pattern is settable at F2 and F3.
Linear: This is a general pattern for constant torque applications.
S-curve: This curve allows the motor to accelerate and decelerate smoothly.
For S-curve, the actual Accel/Decel time takes longer than the time set by user.
►
H17 sets the starting ratio between S-curve and Linear in 1/2 of Accel/Decel Ref.
Frequency. For smooth Accel/Decel starting, increase H17 to extend S-curve ratio.
►
H18 sets the ending ratio between S-curve and Linear in 1/2 of Accel/Decel Ref.
Frequency. For smooth and accurate speed arrival and stopping, increase H18 to
extend S-curve ratio.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...