Advanced functions
128
►
Used when an inverter operates 2 motors connected to two different types of the loads.
►
2
nd
motor operation does not drive 2 motors at the same time.
►
As the figure below, when using two motors with an inverter by exchanging them, select
one motor from 2 motors connected. When 1
st
selected motor operation is stopped,
select a terminal for 2
nd
motor and define H81-H90 parameters to drive the 2
nd
motor.
►
Define the 2nd motor select when a motor is stopped.
►
H81 - H90 parameters function the same as 1
st
motor.
8.23 Frequency setting and 2
nd
drive method select
Group
Code
Parameter Name
Setting
Range
Default Unit
Drive
group
drv
Drive mode 1
-
0 - 3
1
-
Frq
Frequency mode 1
-
0 - 8
0
-
drv2
Drive mode 2
-
0 - 3
1
Frq2
Frequency mode 2
-
0 - 8
0
I/O group
I17-I20
Multi-function input terminal
P1 select
22
0 - 30
Drive mode 1 is used when the input set as 2
nd
source is not entered into multi-input
(I17-I20)
Drive mode 2 can input frequency setting and drive command as a 2
nd
setting value by
using multi-input terminal. In case of driving away from inverter by communication, it is
used when quit the communication and operate by inverter.
The switching method for Drive mode 1 and Drive mode 2 is as follows
If multi-input terminal set as Drive mode 2 is off, it used as Drive mode 1. If multi-input
terminal set as Drive mode 2 is on, it used as Drive mode2.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...