8.15 Regeneration Avoidance Function
The regenerative status can be avoided by detecting the DC Link Voltage level and
raising the frequency to burn out the excessive regenerative energy.
Regenerative energy is occasionally generated due to other fan devices connected in
the same duct.
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 2
F75
RegenAvd Sel
-
0: NO
1: YES
0: NO
F76
RegenAvd Level -
75.0-100.0
87.5
%
F77
ComFreq Limit
-
0-10.00
1.00
Hz
F78
RegenAvd Pgain -
0-100.0
50.0
F79
RegenAvd Igain -
1.0-320.0
50.0
When RegenAvd Level is 100%, DC link voltages are 400V/800V. so when the value is
87.5% by default, the dc voltage to start regen-avoidance function are 350V/700V.
In a regenerative status, DC link voltage will rise, which may is the main cause of
overvoltage alarm. Regenerative status can be avoided by increasing the speed of the
motor when rising of DC link voltage is detected. Overspeed operation is start when the DC
link voltage level exceeds F76_RegenAvd Level.