190
Troubleshooting & Maintenance
Keypad
display
Protective
functions
Descriptions
Electronic
Thermal
The internal electronic thermal of the inverter determines the
overheating of the motor. If the motor is overloaded the inverter
turns off the output. The inverter cannot protect the motor
when driving a motor having more than 4 poles or multi
motors.
Input phase
loss
Inverter output is blocked when one of R, S, T is open or the
electrolytic capacitor needs to be replaced.
Self-diagnostic
malfunction
Displayed when IGBT damage, output phase short, output
phase ground fault or output phase open occurs.
Parameter
save error
Displayed when user-setting parameters fails to be entered
into memory.
Inverter
hardware fault
Displayed when an error occurs in the control circuitry of the
inverter.
Communication
Error
Displayed when the inverter cannot communicate with the
keypad.
Remote
keypad
communication
error
Displayed when inverter and remote keypad does not
communicate each other. It does not stop Inverter operation.
Keypad error
Displayed after Inverter resets keypad when keypad error
occurs and this status is maintained for a certain time.
Cooling fan
fault
Displayed when a fault condition occurs in the inverter cooling
fan.
Instant cut off
Used for the emergency stop of the inverter. The inverter
instantly turns off the output when the EST terminal is turned
on.
The inverter starts to regular operation when turning off the
EST terminal while FX or RX terminal is ON.
External fault A
contact input
When multi-function input terminal (I17-I20) is set to 18
{External fault signal input: A (Normal Open Contact)}, the
inverter turns off the output.
External fault B
contact input
When multi-function input terminal (I17-I20) is set to 19
{External fault signal input: B (Normal Close Contact)}, the
inverter turns off the output.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...