Basic Functions
82
Power On Start select
7.3.7
Group
Code
Parameter Name
Setting
Range
Default Unit
Drive group
drv
[Drive mode]
1, 2
0 - 3
1
Function
group 2
H20
[Power On Start select]
1
0 - 1
0
Set H20 to 1.
When AC input power is applied to the inverter with drv set to 1 or 2 {Run via control
terminal} ON, motor starts acceleration.
This parameter is inactive when drv is set to 0 {Run via keypad} or 3 {RS485
communication}.
Particular attention must be directed to this function due to potential hazard as motor starts to
run suddenly upon applying AC input power.
Restart after fault reset
7.3.8
Group
Code
Parameter Name
Setting
Range
Default Unit
Drive group
drv
[Drive mode]
1, 2
0 - 3
1
Function
group 2
H21
[Restart after fault reset
selection]
1
0 - 1
0
Set H21 to 1.
Motor starts acceleration if
drv
is set to 1 or 2 and the selected terminal is ON when a
fault is cleared.
This parameter is inactive when
drv
is set to 0 {Run via keypad} or 3 {RS485
communication}.
Particular attention must be directed to this function due to potential hazard as motor starts to
run suddenly after the fault is cleared.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...